| Input | Thermocouple(T/C): J, K,T, E, B, R,S, N, C (ITS-90) |
| Pt100Excitation 180uA.2 or 3 wireconnection (ITS-90=0.00385) |
| Voltage-60mVdc to 60mVdcor -10Vdc to10Vdc |
| Current0mA to 24mA |
| SamplingRate | 100mS |
ControlMode | ProportionalBand: 0.0~300.0%(0.0 %=On/Offmode) |
| IntegralTime: 0~3000sec |
| DerivativeTime: 0~1000sec |
| Hysteresis0.0~999.9 or0~9999 |
| CycleTime: 1~60 sec |
Control Output | RelayContact Output2A/240 VAC (Rasistiveload) |
| Pulsed VoltageOutput: DC 0/24V(Rasistive load250 Min.) |
| AlarmOutput | Relay ContactOutput: 2A/240VAC (Rasistiveload) |
| General Specifications | Power supplyUniversal 90~ 265 VAC 50/60Hz |
| Powerconsumption4VA Max. |
| Aux. 24Vdc poweroutput: 25mA(max.) |
| Commonmode rejectionratio: >80dB |
| Operatingtemperature0 to 50°C |
| Humidity0 to 85% RH(Non-CondenseCondition) |
| Electromagneticcompatibility(EMC): En 50081-2,En 50082-2 |
| Housing materialABS plastic.UL 94V0 |
| Weight: 100g |
| DigitalCommunication | EIA RS-485 withModBus RTU modeProtocol |
| Baud Rate: 2400,4800,9600,19200bps |
| 1 Start bit,8 Data bits,None Parity,2 Stop bits |